In this experiment, we will use copper tube water cooling plate to conduct a thermal simulation of 1200w led. Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate in terms of heat dissipation. The experiment will provide two solution.
Send Inquiry

Product Introduction

We hope that our brand and OEM Heat Sink, Liquid Cold Plate for Power Supply, Aluminum Extruded Heatsink for Motor will be more competitive, and our company will get faster development and better benefits. Our good corporate reputation has rapidly expanded our influence in the industry and opened up a broad market space. Our company respects the individuality and pursuit of employees, encourages employees to improve their own abilities, and recognizes the achievements made by employees. Our company has been striving for excellence, accumulating and providing you with "high quality, low price and high efficiency" services with the concept of "quality first and credit".


Thermal Simulation of Water Cooling Plate with Copper Pipe

In this experiment, we will use water cooling plate with copper pipe to conduct a thermal simulation of 1200w led. 

Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate with copper pipe in terms of heat dissipation. The experiment will provide two solution.



Design Input

Cooling method: Forced water cooling

Coolant: Pure water

Ambient temp. Ta: 40℃

LED watt loss: 1114W

Max temp: 50-60℃


1


Design parameter

1. Ambient temp. Ta [°C]: 40C

2. Cabinet temp. Tw [°C]: Unit will be on the top (outside) the cabinet only the glass side will be in the cabinet

3. Cabinet dimension: Unit will be outside the cabinet

4. Power dissipated P[W]: Total Electrical installed power 1500Watt but dissipated around 1200Watt

5. Heat source quantity: Check attached pictures

6. Heat source position and dimension: Check Attached pictures

7. Location of in/outlet water (better to provide system 3D file): Check Attached pictures

8. Accept Max Temp on cold plate [°C]: 50 till 60

9. Installation Hole dimension and position of cold plate: Check the pictures, I have now only 4 holes drawed for assembly the unit the unit till the cabinet. I need a lot of holes for assembly the LED PCB's and Channel Driver and PSU. I want to place alu baseplates to drill all the holes to mount the baseplates I need only a view holes with thread.

10. Liquild Flow rate: _____L/min Depends on what the thermal analysis will tell us what the flow rate must be.

11. Liquid cooling plate Max.size: See Pictures size will be 680x600 but the actual colling area will be 600x540

12. Liquid type: Pure water

13. Temperature of inlet water: Depends on the result of the thermal analysis

14. Temperature of outlet water: Depends on the result of the thermal analysis.

15. Allow Max. pressure of cold plate: Depends on the result of the thermal analysis.


3

4

The model of coolant




5




Solution 1: Velocity of Inlet=0.5m/s(2.7L/min)


6

Temperature of Cool Plate



7

Pressure Drop:5842.6Pa



8

Temperature of Coolant



9(001)

Velocity Vector



Solution 2: Velocity of Inlet=0.3m/s(1.62L/min)


10

Temperature of Cool Plate



11

Pressure Drop:2898.7Pa



12

Temperature of Coolant



13(001)

Velocity Vector


Conclusion

Flow(L/min)

Tmax (0C)

DeltaT (0C)

Delta P (Pa)

Resistance( 0C/W)

2.7L/min

46.817

6.817

5842.6

0.00612

1.62L/min

50.838

10.838

2898.7

0.00973


With this design( Al Cool Plate ), the simulation result of solution meet the Spec.


We have been constantly improving the quality of our PC Liquid Cooling CPU Block Friction Stir Welding Distribution Plate Water Cooling Kit, thereby enhancing the brand image and the company's reputation. We do not seek the best, but we always seek better. We must do better than in the past where we are the first, and we will also strive to make greater improvements than in the past where we cannot be the first. "We are always improving" is the company's common code of conduct. By interacting with our customers, we turn buying and selling into cooperation and elevate business into strategic complementarity.

Hot Tags: Thermal Simulation of Water Cooling Plate with Copper Pipe, China, suppliers, manufacturers, factory, customized, free sample, made in China, Water Cooling Plate with Copper Pipe, High Quality Cooling Heat Sink, OEM Folded Fin Heat Sinks, Copper Skived Heat Sink, Liquid Cold Plate with Copper Tube, Aluminum Extruded Heatsink for Motor