info@awind-cn.com    +86-769-89386135
Cont

Have any Questions?

+86-769-89386135

OEM Aluminum Liquid Water Cooling Block Cold Cooler Plate

OEM Aluminum Liquid Water Cooling Block Cold Cooler Plate

In this experiment, we will use copper tube water cooling plate to conduct a thermal simulation of 1200w led. Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate in terms of heat dissipation. The experiment will provide two solution.
Send Inquiry

Product Introduction

Our company has first-class professional and technical personnel to provide qualified Cooling Plate Heat Sinks, Folded Fin Heat Sink, Round Aluminum Heatsink for LED and professional technical services to our customers through strict control of the production process. We all wish to create win-win deals with our customers, so give us a call today and make a new friend! Innovation is the core value of enterprise seeking rapid development, and it is the ability of enterprise organization system, mechanism, management and technology innovation, which is necessary for enterprise to maintain competitive advantage and growth vitality, and it is the fundamental of enterprise long-term development.


Thermal Simulation of Water Cooling Plate with Copper Pipe

In this experiment, we will use water cooling plate with copper pipe to conduct a thermal simulation of 1200w led. 

Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate with copper pipe in terms of heat dissipation. The experiment will provide two solution.



Design Input

Cooling method: Forced water cooling

Coolant: Pure water

Ambient temp. Ta: 40℃

LED watt loss: 1114W

Max temp: 50-60℃


1


Design parameter

1. Ambient temp. Ta [°C]: 40C

2. Cabinet temp. Tw [°C]: Unit will be on the top (outside) the cabinet only the glass side will be in the cabinet

3. Cabinet dimension: Unit will be outside the cabinet

4. Power dissipated P[W]: Total Electrical installed power 1500Watt but dissipated around 1200Watt

5. Heat source quantity: Check attached pictures

6. Heat source position and dimension: Check Attached pictures

7. Location of in/outlet water (better to provide system 3D file): Check Attached pictures

8. Accept Max Temp on cold plate [°C]: 50 till 60

9. Installation Hole dimension and position of cold plate: Check the pictures, I have now only 4 holes drawed for assembly the unit the unit till the cabinet. I need a lot of holes for assembly the LED PCB's and Channel Driver and PSU. I want to place alu baseplates to drill all the holes to mount the baseplates I need only a view holes with thread.

10. Liquild Flow rate: _____L/min Depends on what the thermal analysis will tell us what the flow rate must be.

11. Liquid cooling plate Max.size: See Pictures size will be 680x600 but the actual colling area will be 600x540

12. Liquid type: Pure water

13. Temperature of inlet water: Depends on the result of the thermal analysis

14. Temperature of outlet water: Depends on the result of the thermal analysis.

15. Allow Max. pressure of cold plate: Depends on the result of the thermal analysis.


3

4

The model of coolant




5




Solution 1: Velocity of Inlet=0.5m/s(2.7L/min)


6

Temperature of Cool Plate



7

Pressure Drop:5842.6Pa



8

Temperature of Coolant



9(001)

Velocity Vector



Solution 2: Velocity of Inlet=0.3m/s(1.62L/min)


10

Temperature of Cool Plate



11

Pressure Drop:2898.7Pa



12

Temperature of Coolant



13(001)

Velocity Vector


Conclusion

Flow(L/min)

Tmax (0C)

DeltaT (0C)

Delta P (Pa)

Resistance( 0C/W)

2.7L/min

46.817

6.817

5842.6

0.00612

1.62L/min

50.838

10.838

2898.7

0.00973


With this design( Al Cool Plate ), the simulation result of solution meet the Spec.


We produce our OEM Aluminum Liquid Water Cooling Block Cold Cooler Plate according to batch management, from the molding process all the way to the packaging process according to the box batch barcode management to ensure the traceability of quality. We are committed to managing the feelings of the team, sharing the benefits of the operation, and enhancing the value of the team's operation, so that the company's strategies and goals can be achieved and sustained! Our company relies on the scientific management system, exquisite production technology, perfect detection means, good enterprise honor, has won the praise and praise of the majority of users.

Hot Tags: Thermal Simulation of Water Cooling Plate with Copper Pipe, China, suppliers, manufacturers, factory, customized, free sample, made in China, Zippered Fin Heat Sinks, Aluminum Extrusion Profiles Heat Sink, High Quality Heat Sink, Vapor Chamber, Bonded Fin Heat Sinks Assemblies, Liquid Cold Plate

[[ProKeywords]]

Send Inquiry