High Precision Liquid Cooling Plate with Copper Tube

In this experiment, we will use copper tube water cooling plate to conduct a thermal simulation of 1200w led. Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate in terms of heat dissipation. The experiment will provide two solution.
Send Inquiry

Product Introduction

Since the establishment of our company, we have always followed the tenet of quality and integrity, and have been developing new Water Cooling Plate with Copper Pipe, Folded Fin Heat Sink, Bonded Fin Heat Sinks Assemblies to meet the diversified needs of our customers. With the corporate tenet of quality first, reputation first, sincerely recruiting customers from all over the world, our company wholeheartedly serves the majority of users and sincerely welcomes new and old users from all over the country to come to our company to negotiate business. Our goal is to become a leading enterprise in resource allocation of leading industries, leading the development of global production technology, and having voice and influence in the global market. Over the past few years, we have constantly adjusted and improved equipment and technology to make our products perfect and better serve every customer. We continue to innovate technology, innovative products, innovative management, healthy, sustainable and rapid development of enterprises.


Thermal Simulation of Water Cooling Plate with Copper Pipe

In this experiment, we will use water cooling plate with copper pipe to conduct a thermal simulation of 1200w led. 

Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate with copper pipe in terms of heat dissipation. The experiment will provide two solution.



Design Input

Cooling method: Forced water cooling

Coolant: Pure water

Ambient temp. Ta: 40℃

LED watt loss: 1114W

Max temp: 50-60℃


1


Design parameter

1. Ambient temp. Ta [°C]: 40C

2. Cabinet temp. Tw [°C]: Unit will be on the top (outside) the cabinet only the glass side will be in the cabinet

3. Cabinet dimension: Unit will be outside the cabinet

4. Power dissipated P[W]: Total Electrical installed power 1500Watt but dissipated around 1200Watt

5. Heat source quantity: Check attached pictures

6. Heat source position and dimension: Check Attached pictures

7. Location of in/outlet water (better to provide system 3D file): Check Attached pictures

8. Accept Max Temp on cold plate [°C]: 50 till 60

9. Installation Hole dimension and position of cold plate: Check the pictures, I have now only 4 holes drawed for assembly the unit the unit till the cabinet. I need a lot of holes for assembly the LED PCB's and Channel Driver and PSU. I want to place alu baseplates to drill all the holes to mount the baseplates I need only a view holes with thread.

10. Liquild Flow rate: _____L/min Depends on what the thermal analysis will tell us what the flow rate must be.

11. Liquid cooling plate Max.size: See Pictures size will be 680x600 but the actual colling area will be 600x540

12. Liquid type: Pure water

13. Temperature of inlet water: Depends on the result of the thermal analysis

14. Temperature of outlet water: Depends on the result of the thermal analysis.

15. Allow Max. pressure of cold plate: Depends on the result of the thermal analysis.


3

4

The model of coolant




5




Solution 1: Velocity of Inlet=0.5m/s(2.7L/min)


6

Temperature of Cool Plate



7

Pressure Drop:5842.6Pa



8

Temperature of Coolant



9(001)

Velocity Vector



Solution 2: Velocity of Inlet=0.3m/s(1.62L/min)


10

Temperature of Cool Plate



11

Pressure Drop:2898.7Pa



12

Temperature of Coolant



13(001)

Velocity Vector


Conclusion

Flow(L/min)

Tmax (0C)

DeltaT (0C)

Delta P (Pa)

Resistance( 0C/W)

2.7L/min

46.817

6.817

5842.6

0.00612

1.62L/min

50.838

10.838

2898.7

0.00973


With this design( Al Cool Plate ), the simulation result of solution meet the Spec.


The remarkable quality, perfect faith, and endless pursuit cause our High Precision Liquid Cooling Plate with Copper Tube form a strong comprehensive strength in the marketplace. Our company practices green production, promotes circular economy, advances energy conservation and emission reduction, and develops environmentally friendly products. Our quality assurance system is perfect, the production process is strictly controlled, the technology is mature and advanced, and the main production and testing equipment is at the leading level in China.

Hot Tags: Thermal Simulation of Water Cooling Plate with Copper Pipe, China, suppliers, manufacturers, factory, customized, free sample, made in China, Cooling Plate Heat Sinks, Industrial Water Cooling Cold Plate, Aluminum Cold Plates for Battery, Cold Forged Heat Sink, Folded Fin Heat Sink, High Quality Cooling Heat Sink