Custom Friction Stir Welding Water Cooling Plate Laser Equipment Cold Plate

In this experiment, we will use copper tube water cooling plate to conduct a thermal simulation of 1200w led. Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate in terms of heat dissipation. The experiment will provide two solution.
Send Inquiry

Product Introduction

Our team is working hard to optimize our own processes to improve development efficiency and add more humanized features to our Zippered Fin Heat Sinks, Industrial Water Cooling Cold Plate, Liquid Cold Plate with Copper Tube. With the development of the business and the huge demands of the society, we become more multifunctional in recent years, and set up all sorts of businesses to meet the needs of our clients. Striving to be the mainstream of the industry is the purpose, so we do the industry enterprise leader by over taking the lead in development, superhero step. We regard providing both material and spiritual happiness for our employees as well as providing a better and bigger development platform as our core values. We have strengthened our ability to compete in the market and seize the first opportunity to compete in the industry.


Thermal Simulation of Water Cooling Plate with Copper Pipe

In this experiment, we will use water cooling plate with copper pipe to conduct a thermal simulation of 1200w led. 

Through the temperature graph, pressure graph, Velocity Vector, etc, you can better see the effect of the water cooling plate with copper pipe in terms of heat dissipation. The experiment will provide two solution.



Design Input

Cooling method: Forced water cooling

Coolant: Pure water

Ambient temp. Ta: 40℃

LED watt loss: 1114W

Max temp: 50-60℃


1


Design parameter

1. Ambient temp. Ta [°C]: 40C

2. Cabinet temp. Tw [°C]: Unit will be on the top (outside) the cabinet only the glass side will be in the cabinet

3. Cabinet dimension: Unit will be outside the cabinet

4. Power dissipated P[W]: Total Electrical installed power 1500Watt but dissipated around 1200Watt

5. Heat source quantity: Check attached pictures

6. Heat source position and dimension: Check Attached pictures

7. Location of in/outlet water (better to provide system 3D file): Check Attached pictures

8. Accept Max Temp on cold plate [°C]: 50 till 60

9. Installation Hole dimension and position of cold plate: Check the pictures, I have now only 4 holes drawed for assembly the unit the unit till the cabinet. I need a lot of holes for assembly the LED PCB's and Channel Driver and PSU. I want to place alu baseplates to drill all the holes to mount the baseplates I need only a view holes with thread.

10. Liquild Flow rate: _____L/min Depends on what the thermal analysis will tell us what the flow rate must be.

11. Liquid cooling plate Max.size: See Pictures size will be 680x600 but the actual colling area will be 600x540

12. Liquid type: Pure water

13. Temperature of inlet water: Depends on the result of the thermal analysis

14. Temperature of outlet water: Depends on the result of the thermal analysis.

15. Allow Max. pressure of cold plate: Depends on the result of the thermal analysis.


3

4

The model of coolant




5




Solution 1: Velocity of Inlet=0.5m/s(2.7L/min)


6

Temperature of Cool Plate



7

Pressure Drop:5842.6Pa



8

Temperature of Coolant



9(001)

Velocity Vector



Solution 2: Velocity of Inlet=0.3m/s(1.62L/min)


10

Temperature of Cool Plate



11

Pressure Drop:2898.7Pa



12

Temperature of Coolant



13(001)

Velocity Vector


Conclusion

Flow(L/min)

Tmax (0C)

DeltaT (0C)

Delta P (Pa)

Resistance( 0C/W)

2.7L/min

46.817

6.817

5842.6

0.00612

1.62L/min

50.838

10.838

2898.7

0.00973


With this design( Al Cool Plate ), the simulation result of solution meet the Spec.


We focus on product development and technological innovation, and design and produce our Custom Friction Stir Welding Water Cooling Plate Laser Equipment Cold Plate with scientific and stable concepts. We have always regarded excellence as our way of survival and have always made it an integral part of our company's Creed. We establish product advantages, highlight market benefits, accelerate capital turnover, ensure product quality and optimize internal mechanisms.

Hot Tags: Thermal Simulation of Water Cooling Plate with Copper Pipe, China, suppliers, manufacturers, factory, customized, free sample, made in China, Bonded Fin Heat Sinks Assemblies, Liquid Cold Plate with Copper Tube, Vapor Chamber Heat Sink, Vapor Chamber, Heatsink Design, AL Extrusion Heat Sink